Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

45

Programming and Parameters

Chapter 1

UT

IL

IT

Y

MOP Con

fig

194 [Save MOP Ref]

Enables/disables the feature that saves the present MOP frequency reference at power down or at
stop.

195 [MOP Rate]

Sets rate of change of the MOP reference in
response to a digital input.

Default:

Min/Max:

Units:

1.0 Hz/s
30.0 RPM/s

0.2/[Maximum Freq]
6.0/[Maximum Freq]
0.1 Hz/s
0.1 RPM/s

Dr

iv

e M

em

or

y

196 [Param Access Lvl]

Selects the parameter display level viewable on
the HIM.
Basic = Reduced parameter set
Advanced = Full parameter set
Reserved = Full parameter set and

Engineering parameters (refer to the
PowerFlex Reference Manual).

This parameter is not reset when “Reset to
Defaults” is selected.

Default:

Options:

0

0
1
2

“Basic”

“Basic”
“Advanced”
“Reserved”

197 [Reset To Defalts]

Resets parameters to factory defaults except [Mtr
NP Pwr Units], [Speed Units], [Param Access Lvl],
[Language], [Voltage Class] & [TorqProve Cnfg]
(params 46, 79, 196, 201, 202 & 600).
Option 1 resets parameters to factory defaults

based on [Voltage Class].

Options 2 & 3 will set [Voltage Class] to low or

high and reset parameters to corresponding
factory defaults.

Important: Frames 5 & 6 - the internal fan
voltage may have to be changed when using
Option 2 or 3. See “Selecting /Verifying Fan
Voltage” in the Installation Instructions,
publication

20B-IN0019

.

Default:

Options:

0

0
1
2
3

“Ready”

“Ready”
“Factory”
“Low Voltage”
“High Voltage”

041

047
054
055
062
063
069

072
082
148
158

198 [Load Frm Usr Set]

Loads a previously saved set of parameter values
from a selected user set location in drive
nonvolatile memory to active drive memory.

Default:

Options:

0

0
1
2
3

“Ready”

“Ready”
“User Set 1”
“User Set 2”
“User Set 3”

199

199 [Save To User Set]

Saves the parameter values in active drive
memory to a user set in drive nonvolatile
memory.

Default:

Options:

0

0
1
2
3

“Ready”

“Ready”
“User Set 1”
“User Set 2”
“User Set 3”

198

200 [Reset Meters]

Resets selected meters to zero.

Default:

Options:

0

0
1
2

“Ready”

“Ready”
“MWh”
“Elapsed Time”

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 16

for symbol descriptions

Values

Rela

ted

0

x

x

0

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 = Save

0 = Do Not Save
x = Reserved

Bit #

Factory Default Bit Values

At P

owr D

own

At

St

op