Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual

Page 71

Advertising
background image

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

71

Programming and Parameters

Chapter 1

APPLIC

AT

IONS

Adju

st

V

ol

ta

ge

670 [Adj Volt Trim Hi]

Scales the upper value of the [Adj Volt TrimSel]
selection when the source is an analog input.

Default:

Min/Max:
Units:

100.0%

0.0/100.0% of Drive Rated Volts
0.1%

671 [Adj Volt Trim Lo]

Scales the lower value of the [Adj Volt TrimSel]
selection when the source is an analog input.

Default:

Min/Max:
Units:

0.0%

0.0/100.0% of Drive Rated Volts
0.1%

672 [Adj Volt Trim %]

Scales the total voltage trim value from all
sources. Analog In 1 & 2 are scaled separately
with [Adj Volt Trim Hi] & [Adj Volt Trim Lo] then
[Adj Volt Trim %] sets the trim value. The sign of
this value will determine if trim is added or
subtracted from the reference.

Default:

Min/Max:
Units:

0.0%

–/+100.0% of Drive Rated Volts
0.1%

675 [Adj Volt AccTime]

Sets the rate of voltage increase. The value will
be the time it takes to ramp the voltage from
[Min Adj Voltage] to [Maximum Voltage]. An “S”
curve can be applied to the ramp using
parameter 677.

Default:

Min/Max:
Units:

0.0 Secs

0.0/3600.0 Secs
0.1 Secs

676 [Adj Volt DecTime]

Sets the rate of voltage decrease. The value will
be the time it takes to ramp the voltage from
[Maximum Voltage] to [Min Adj Voltage]. An “S”
curve can be applied to the ramp using [Adj Volt
Scurve]. Important: This ramp and [Decel Time
1/2] (parameters 142/143) must ramp to zero for
drive to Stop.

Default:

Min/Max:
Units:

0.0 Secs

0.0/3600.0 Secs
0.1 Secs

677 [Adj Volt S Curve]

Sets the percentage of accel or decel time to be
applied to the voltage ramp as “S” curve. Time is
added 1/2 at the beginning and 1/2 at the end.

Default:

Min/Max:
Units:

0.0%

0.0/100.0%
0.1%

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 16

for symbol descriptions

Values

Rela

ted