32

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

Chapter 1

Programming and Parameters

SPEED C

O

MMAND

Speed Ref

eren

ce

s

096 [TB Man Ref Sel]

Sets the manual speed reference source when a
digital input (parameter 361…366) is
configured for “Auto/Manual” or “Manual/Auto”
(v7.002 & later).

(1)

“Analog In 2” is not a valid selection if it was
selected for any of the following:
- [Trim In Select]
- [PI Feedback Sel]
- [PI Reference Sel]
- [Current Lmt Sel]
- [Sleep-Wake Ref]

Default:

Options:

1

1
2
3-8
9
10-17
18
19
20

“Analog In 1”

“Analog In 1”
“Analog In 2”

(1)

“Reserved”
“MOP Level”
“Reserved”
“DPI Port 1”

(2)

“DPI Port 2”

(2)

“DPI Port 3”

(2)

097
098

(2)

Requires a Series B HIM with firmware v5.004 or greater.
Selects the HIM to provide the manual speed reference when a digital input is configured for “Auto/
Manual” or “Manual/Auto.”
Additionally, if [Man Ref Preload], parameter 193 is set to “Enabled,” the automatic speed reference will
be preloaded into the HIM when the drive switches to Manual mode from Automatic mode (or to
Automatic mode from Manual mode).
• Set [Save HIM Ref], parameter 192, bit 1 (Manual Mode) as desired.
• Set [TB Man Ref Sel] to the desired drive reference when in Manual Mode. If set to one of the DPI

Ports, then [Man Ref Preload] must be set to enable or disable reference preload of the current speed.
Connect a HIM to the DPI Port selected.

• When Manual mode is requested through the terminal block digital input, the drive evaluates if

Manual mode can be granted.

• If [TB Man Ref Sel] is set to a DPI Port and [Man Ref Preload] is enabled, the drive transfers the last

value of the automatic speed reference to the HIM. The HIM is now the speed reference source. The
terminal block has exclusive control based on [Save HIM Ref], bit 1 (Manual Mode). If [Man Ref
Preload] is disabled, the HIM is now the speed reference source. The terminal block has exclusive
control based on [Save HIM Ref], bit 1 (Manual Mode).

Important: the HIM does not enter Manual mode, it is only the reference source for the terminal block.
When Auto mode is requested through the terminal block, the drive changes to Auto mode and returns
control and reference to the previous state before Manual mode was requested.

097 [TB Man Ref Hi]

Scales the upper value of the [TB Man Ref Sel]
selection when the source is an analog input.

Default:

Min/Max:
Units:

[Maximum Speed]

–/+[Maximum Speed]
0.1 Hz
0.01 RPM

079
096

098 [TB Man Ref Lo]

Scales the lower value of the [TB Man Ref Sel]
selection when the source is an analog input.

Default:

Min/Max:
Units:

0.0

–/+[Maximum Speed]
0.1 Hz
0.01 RPM

079
096

099 [Pulse Input Ref]

Displays the pulse input value as seen at
terminals 5 and 6 of the Encoder Terminal Block,
if [Encoder Z Chan], parameter 423 is set to
“Pulse Input.”

Default:

Min/Max:

Units:

Read Only

–/+420.0 Hz
–/+25200.0 RPM
0.1 Hz
0.1 RPM

D

is

cre

te

S

pee

ds

100 [Jog Speed 1]

Sets the output frequency when Jog Speed 1 is
selected.

Default:

Min/Max:
Units:

10.0 Hz
300.0 RPM

–/+[Maximum Speed]
0.1 Hz
1 RPM

079

101
102
103
104
105
106
107

[Preset Speed 1]
[Preset Speed 2]
[Preset Speed 3]
[Preset Speed 4]
[Preset Speed 5]
[Preset Speed 6]
[Preset Speed 7]

Provides an internal fixed speed command value.
In bipolar mode direction is commanded by the
sign of the reference.

Default:

Min/Max:
Units:

5.0 Hz/150 RPM
10.0 Hz/300 RPM
20.0 Hz/600 RPM
30.0 Hz/900 RPM
40.0 Hz/1200 RPM
50.0 Hz/1500 RPM
60.0 Hz/1800 RPM

–/+[Maximum Speed]
0.1 Hz
1 RPM

079
090
093

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 16

for symbol descriptions

Values

Rela