215 [Last Stop Source]

Displays the source that initiated the most recent
stop sequence. It will be cleared (set to 0) during
the next start sequence.

(1)

Options not listed are reserved for future use.

Default:

Options:

(1)

0
1-5
7
8
9
10
11
12
13

Read Only

“Pwr Removed”
“DPI Port 1-5”
“Digital In”
“Fault”
“Not Enabled”
“Sleep”
“Jog”
“Autotune”
“Precharge”

361
362
363
364
365
366

216 [Dig In Status]

Status of the digital inputs.

Read Only

361

366

217 [Dig Out Status]

Status of the digital outputs.

Read Only

380

384

218 [Drive Temp]

Present operating temperature of the drive
power section.

Default:

Min/Max:
Units:

Read Only

0.0/100.0%
0.1%

219 [Drive OL Count]

Accumulated percentage of drive overload.
Continuously operating the drive over 100% of its
rating will increase this value to 100% and cause
a drive fault or foldback depending on the
setting of [Drive OL Mode].

Default:

Min/Max:
Units:

Read Only

0.0/100.0%
0.1%

150

220 [Motor OL Count]

Accumulated percentage of motor overload.
Continuously operating the motor over 100% of
the motor overload setting will increase this
value to 100% and cause a drive fault. Refer to
page

123

.

Default:

Min/Max:
Units:

Read Only

0.0/100.0%
0.1%

047
048

221 [Mtr OL Trip Time]

Amount of time before a Drive Overload fault
(F64) occurs if the load condition remains
constant. A value of 99999 means that the drive
is operating under the overload level.

Default:

Min/Max:
Units:

Read Only

0/99999
1

220

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 16

for symbol descriptions

Values

Rela

ted

0

0

0

0

0

0

x

x

0

0

0

0

0

0

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 = Input Present

0 = Input Not Present
x = Reserved

Bit #

Digital In1

Digital In2

Digital In3

Digital In4

Digital In5

Digital In6

In1 DL

ogRslt

(1)

In2 DL

ogRslt

(1)

In3 DL

ogRslt

(1)

In4 DL

ogRslt

(1)

In5 DL

ogRslt

(1)

In6 DL

ogRslt

(1)

(1)

Firmware 6.002 and later.

0

0

x

0

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 = Output Energized

0 = Output De-energized
x = Reserved

Bit #

Digital O

ut1

Digital O

ut2

Digital O

ut3

Advertising