Application Notes

Appendix C

Drive Setup

TorqProve with Encoder

To Enable TorqProve with an encoder, bit 0 of [TorqProve Cnfg], parameter 600
must be set to “1.” Once this is set, a Type 2 alarm will be active until the
following settings are entered:

In addition, [Stop Mode A/B], parameters 155/156 must be set to option “1,
Ramp” and [DC Brake Time], parameter 159 must be set to “0.0 Secs.”

Encoderless TorqProve

To Enable Encoderless TorqProve, both bits 0 and 1 of [TorqProve Cnfg],
parameter 600 must be set to “1.” Once this is set, a Type 2 alarm will be active
until the following settings are entered:

In addition, [Stop Mode A/B], parameters 155/156 must be set to option “1,
Ramp” and [DC Brake Time], parameter 159 must be set to “0.0 Secs.”

Encoderless Guidelines

You can not hold zero speed in encoderless mode or operate near zero speed
because of this, it is very important to set [Minimum Speed], parameter 81 to

two or three times the slip frequency when in encoderless mode. (Example: A
1740 RPM motor has 2 Hz of slip. Set [Minimum Speed] to 4…6 Hz.)

In addition, [Stop Mode A/B], parameters 155/156 must be set to option “1,
Ramp” and [DC Brake Time], parameter 159 must be set to “0.0 Secs.”

Also set [Float Tolerance], parameter 606 to

one to three times the slip

frequency when in encoderless mode. You should also use fast accel and decel
times (less than 2 seconds) when operating in encoderless mode.

No.

Name

Value

Notes

053

[Motor Cntl Sel]

“4, FVC Vector”

080

[Feedback Select]

“3, Encoder”

412

[Motor Fdbk Type]

“1, Quad Check”

No.

Name

Value

Notes

053

[Motor Cntl Sel]

“4, FVC Vector” or
“0, Sensrls Vect”

080

[Feedback Select]

“1, Slip Comp”