Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

Chapter 1

Programming and Parameters

MO

TO

R

C

O

N

TROL

Spee

d F

eedback

413 [Encoder PPR]

Contains the encoder pulses per revolution. For
improved operation in FVC Vector mode, PPR
should be ³ (64 x motor poles).

Default:

Min/Max:
Units:

1024 PPR

2/20000 PPR
1 PPR

414 [Enc Position Fdbk]

Displays raw encoder pulse count. For single
channel encoders, this count will increase (per
rev.) by the amount in [Encoder PPR]. For
quadrature encoders this count will increase by 4
times the amount defined in [Encoder PPR]. A
power cycle is required to reset this value.

Default:

Min/Max:
Units:

Read Only

–/+2147483647
1

415 [Encoder Speed]

Provides a monitoring point that reflects speed
as seen from the feedback device.

Default:

Min/Max:

Units:

Read Only

–/+420.0 Hz
–/+25200.0 RPM
0.1 Hz
0.1 RPM

079

416 [Fdbk Filter Sel]

Selects the type of feedback filter desired.
“Light” uses a 35/49 radian feedback filter.
“Heavy” uses a 20/40 radian feedback filter.

Default:

Options:

0

0
1
2

“None”

“None”
“Light”
“Heavy”

419 [Notch FilterFreq]

Sets the center frequency for an optional 2-pole
notch filter. Filter is applied to the torque
command. “0” disables this filter.

Default:

Min/Max:
Units:

0.0 Hz

0.0/500.0 Hz
0.1 Hz

053

420 [Notch Filter K]

Sets the gain for the 2-pole notch filter.

Default:

Min/Max:
Units:

0.3 Hz

0.1/0.9 Hz
0.1 Hz

053

421 [Marker Pulse]

Latches the raw encoder count at each marker
pulse.

Default:

Min/Max:
Units:

Read Only

–/+2147483647
1

422 [Pulse In Scale]

Sets the scale factor/gain for the Pulse Input
when P423 is set to “Pulse Input.” Calculate for
the desired speed command as follows:

Default:

Min/Max:
Units:

64

2/20000
1

423 [Encoder Z Chan]

Defines if the input wired to terminals 5 & 6 of
the Encoder Terminal Block will be used as a
Pulse or Marker input. Options 1 & 3 detect a loss
of signal (when using differential inputs)
regardless of the [Feedback Select], param. 080
setting. When option 2 or 3 is used with Profile/
Indexer mode, the “homing” routine will position
to the nearest marker pulse off of the home limit
switch.

Default:

Options:

0

0
1
2
3

“Pulse Input”

“Pulse Input”
“Pulse Check”
“Marker Input”
“Marker Check”

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 16

for symbol descriptions

Values

Rela

ted

FV

FV

Input Pulse Rate (Hz)

Desired Cmd. (Hz)

Input Pulse Rate (Hz)

Desired Cmd. (RPM)

x

120

[Motor Poles]

for Hz, [Pulse In Scale] =

for RPM, [Pulse In Scale] =