Speed Command File

Fi

le

Grou

p

No

.

Parameter Name & Description

See

page 16

for symbol descriptions

Values

Re

la

te

d

SPEED C

O

MMAND

Spd Mod

e & Lim

its

079 [Speed Units]

Selects the units to be used for all speed related
parameters. Options 0 & 1 indicate status only. 2
& 3 will convert/configure the drive for that
selection.

“Convert Hz” (2) - converts all speed based
parameters to Hz, and changes the value
proportionately (i.e. 1800 RPM = 60 Hz).

“Convert RPM” (3) - converts all speed based
parameters to RPM, and changes the value
proportionately.

This parameter is not reset when “Reset to
Defaults” is selected.

Default:

Options:

0

0
1
2
3

“Hz”

“Hz”
“RPM”
“Convert Hz”
“Convert RPM”

080 [Feedback Select]

Selects the source for motor speed feedback.
Note that all selections are available when using
Process PI.

“Open Loop” (0) - no encoder is present, and slip
compensation is not needed.

“Slip Comp” (1) - tight speed control is needed,
and encoder is not present.

“Encoder” (3) - an encoder is present.

“Simulator” (5) - Simulates a motor for testing
drive operation & interface check.

Default:

Options:

0

0
1
2
3
4
5

“Open Loop”

“Open Loop”
“Slip Comp”
“Reserved”
“Encoder”
“Reserved”
“Simulator”

412
152

081 [Minimum Speed]

Sets the low limit for speed reference after
scaling is applied. Refer to parameter 083
[Overspeed Limit].

Default:

Min/Max:
Units:

0.0

0.0/[Maximum Speed]
0.1 Hz
0.1 RPM

079
083
092
095

082 [Maximum Speed]

Sets the high limit for speed reference after
scaling is applied. Refer to parameter 083
[Overspeed Limit].

Default:

Min/Max:

Units:

50.0 or 60.0 Hz (volt class)
[Motor NP RPM]

5.0/420.0 Hz
75.0/24000.0 RPM
0.1 Hz
0.1 RPM

055
079
083
091
094
202

083 [Overspeed Limit]

Sets the incremental amount of the output
frequency (above [Maximum Speed]) allowable
for functions such as slip compensation.
[Maximum Speed] + [Overspeed Limit] must be

≤ [Maximum Freq]

Default:

Min/Max:

Units:

10.0 Hz
300.0 RPM

0.0/20.0 Hz
0.0/600.0 RPM
0.1 Hz
0.1 RPM

055
079
082

Frequency

Output

Voltage

Overspeed

Limit

Frequency Trim
due to Speed
Control Mode

Maximum

Voltage

Motor NP

Voltage

Run

Boost

Break

Voltage

Start

Boost

Allowable Output Frequency Range - Normal Operation

Allowable Speed Reference Range

Allowable Output Frequency Range -

Bus Regulation or Current Limit

Maximum

Frequency

Motor NP Hz

0

Break

Frequency

Maximum

Speed

Minimum

Speed

Output

Frequency

Limit

(lower limit on this range can be 0 depending on the value of Speed Adder)