Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual
Page 152

152
Rockwell Automation Publication 20B-UM002G-EN-P - July 2014
Appendix D
Instructions for ATEX Approved Drives in Group II Category (2) G D Applications with ATEX Approved Motors
22. Remake continuity of the over temperature circuit connected to the drive’s
digital inputs. The drive should remain stopped and in an Auxiliary Input
fault condition.
23. Provide the command to restart the drive. In the case of a maintained start,
remove and reapply the start command. The drive should remain stopped
and in an Auxiliary Input fault condition.
24. Provide a fault reset command to the drive. The drive fault should clear but
the drive should not restart.
25. Provide the command to restart the drive. The drive should run normally.
26. Stop the drive and disconnect all power including external control power.
27. Remove the test mechanism, reconnect original wires and verify all wiring.
28. Reconnect the motor to the load if it had been previously disconnected.
29. Check for proper operation.