Motor control file – Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual

Page 23

Advertising
background image

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

23

Programming and Parameters

Chapter 1

Motor Control File

Fi

le

Grou

p

No

.

Parameter Name & Description

See

page 16

for symbol descriptions

Values

Re

la

te

d

MOT

O

R

CONTROL

Mo

tor D

at

a

040 [Motor Type]

Set to match the type of motor connected.

(1)

Important: Selecting option 1 or 2 also

requires selection of “Custom V/Hz,” option 2 in
parameter 53.

Default:

Options:

0

0
1
2

“Induction”

“Induction”
“Synchr Reluc”

(1)

“Synchr PM”

(1)

053

041 [Motor NP Volts]

Set to the motor nameplate rated volts.

Default:

Min/Max:
Units:

Based on Drive Rating

0.0/[Rated Volts]
0.1 VAC

042 [Motor NP FLA]

Set to the motor nameplate rated full load amps.

Default:

Min/Max:
Units:

Based on Drive Rating

0.0/[Rated Amps] x 2
0.1 Amps

047
048

043 [Motor NP Hertz]

Set to the motor nameplate rated frequency.

Default:

Min/Max:
Units:

Based on Drive Cat. No.

5.0/400.0 Hz
0.1 Hz

044 [Motor NP RPM]

Set to the motor nameplate rated RPM.

Default:

Min/Max:
Units:

1750.0 RPM

60.0/24000.0 RPM
1.0 RPM

045 [Motor NP Power]

Set to the motor nameplate rated power.

Default:

Min/Max:
Units:

Based on Drive Rating

0.00/1000.00
0.01 kW/HP
See

[Mtr NP Pwr Units]

046

046 [Mtr NP Pwr Units]

Selects the motor power units to be used. This
parameter is not reset when “Reset to Defaults”
is selected.
“Convert HP” = converts all power units to
Horsepower.
“Convert kW” = converts all power units to
kilowatts.

Default:

Options:

0
1
2
3

Drive Rating Based

“Horsepower”
“kiloWatts”
“Convert HP”
“Convert kW”

047 [Motor OL Hertz]

Selects the output frequency below which the
motor operating current is derated. The motor
thermal overload will generate a fault at lower
levels of current.

Default:

Min/Max:
Units:

Motor NP Hz/3

0.0/Motor NP Hz
0.1 Hz

042
220

048 [Motor OL Factor]

Sets the operating level for the motor overload.

Default:

Min/Max:
Units:

1.00

0.20/2.00
0.01

042
220

049 [Motor Poles]

Defines the number of poles in the motor.

Default:

Min/Max:
Units:

4

2/40
1 Pole

To

rq

A

tt

ribu

tes

050

[Motor OL Mode]

Provides the ability to preserve the [Motor OL Count] value through a power cycle or drive reset.

Option Descriptions
Pwr Cyc Ret

If bit 0 is set to “0” (Disabled) the value of [Motor OL Count], parameter 220 is
reset to zero by a drive reset or power cycle. A “1” (Enabled) will maintain the
value. A transition from “1” to “0” resets [Motor OL Count] to zero.

Motor

FLA

OL

Factor

Operating

Level

=

x

v6

x

x

x

0

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 = Enabled

0 = Disabled
x = Reserved

Bit #

Factory Default Bit Values

Pwr C

yc Ret

Advertising