Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual

Page 87

Advertising
background image

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

87

Troubleshooting

Chapter 2

Ground Fault

13

1 A current path to earth ground greater

than 25% of drive rating.

Check the motor and external wiring to the
drive output terminals for a grounded
condition.

Hardware Fault

93

Hardware enable is disabled (jumpered
high) but logic pin is still low.

1. Check jumper.
2. Replace Main Control Board.

Hardware Fault

130

Gate array load error.

1. Cycle power.
2. Replace Main Control Board.

Hardware Fault

131

Dual port failure.

1. Cycle power.
2. Replace Main Control Board.

Hardware PTC

18

Motor PTC (Positive Temperature
Coefficient) Overtemp.

Heatsink LowTemp

10

1 Annunciates a too low temperature

case or an open NTC (heatsink
temperature sensing device) circuit.

1. Verify ambient temperature.
2. In cold ambient temperatures, add

space heaters.

Heatsink OvrTemp

8

1 Heatsink temperature exceeds 100% of

[Drive Temp] or is less than
approximately -19 °C.

1. Verify that maximum ambient

temperature has not been exceeded.

2. Check fan.
3. Check for excess load.
4. In cold ambient temperatures, add

space heaters.

HW OverCurrent

12

1 The drive output current has exceeded

the hardware current limit.

Check programming. Check for excess load,
improper DC boost setting, DC brake volts
set too high or other causes of excess
current.

Incompat MCB-PB

106

2 Drive rating information stored on the

power board is incompatible with the
main control board.

1. Load compatible version files into drive.
2. Frame 7…10 drives must have

firmware version 4.009 or greater.

I/O Comm Loss

121

I/O Board lost communications with the
Main Control Board.

Check connector. Check for induced noise.
Replace I/O board or Main Control Board.

I/O Failure

122

I/O was detected, but failed the
powerup sequence.

Replace Main Control Board.

Input Phase Loss

17

The DC bus ripple has exceeded a preset
level.

Check incoming power for a missing
phase/blown fuse.

IR Volts Range

77

“Calculate” is the autotune default and
the value determined by the autotune
procedure for IR Drop Volts is not in the
range of acceptable values.

Re-enter motor nameplate data.

IXo VoltageRange

87

Voltage calculated for motor inductive
impedance exceeds 25% of [Motor NP
Volts].

1. Check for proper motor sizing.
2. Check for correct programming of

[Motor NP Volts], parameter 41.

3. Additional output impedance can be

required.

Load Loss

15

Drive output torque current is below
[Load Loss Level] for a time period
greater than [Load Loss time].

1. Verify connections between motor and

load.

2. Verify level and time requirements.

Motor Overload

7

1
3

Internal electronic overload trip.
Enable/Disable with [Fault Config 1] on

page 52

.

An excessive motor load exists. Reduce
load so drive output current does not
exceed the current set by [Motor NP FLA].

Motor Thermistor

16

Thermistor output is out of range.

1. Verify that thermistor is connected.
2. Motor is overheated. Reduce load.

NVS I/O Checksum

109

EEprom checksum error.

1. Cycle power and repeat function.
2. Replace Main Control Board.

NVS I/O Failure

110

EEprom I/O error.

1. Cycle power and repeat function.
2. Replace Main Control Board.

Fault

No

.

Ty

pe

(1)

Description

Action

v6