Programming and Parameters

Chapter 1

DYNAMIC

C

ONTROL

Load Limits

153 [Regen Power Limit]

Sets the maximum power limit allowed to
transfer from the motor to the DC bus. When
using an external dynamic brake, set this
parameter to its maximum value.

Default:

Min/Max:
Units:

–50.0%

–800.0/0.0%
0.1%

053

154 [Current Rate Limit]

Sets the largest allowable rate of change for the
current reference signal. This number is scaled in
percent of maximum motor current every 250
microseconds.

Default:

Min/Max:
Units:

400.0%

1.0/800.0%
0.1%

053

St

op/Brak

e Modes

145 [DB While Stopped]

Enables/disables dynamic brake operation when
drive is stopped. DB can operate if input voltage
becomes too high.
Disabled = DB will only operate when drive is
running.
Enable = DB can operate whenever drive is
energized.

Default:

Options:

0

0
1

“Disabled”

“Disabled”
“Enabled”

161
162

155
156

[Stop Mode A]
[Stop Mode B]

Active stop mode. [Stop Mode A] is active unless
[Stop Mode B] is selected by inputs.

(1)

When using options 1, 2 or 4, refer to parameter 158

Attention statements.

Default:
Default:

Options:

1
0

0
1
2
3
4

“Ramp”
“Coast”

“Coast”
“Ramp”

(1)

“Ramp to Hold”

(1)

“DC Brake”
“Fast Brake”

(1)

157
158
159

157 [DC Brake Lvl Sel]

Selects the source for [DC Brake Level].

Default:

Options:

0

0
1
2

“DC Brake Lvl”

“DC Brake Lvl”
“Analog In 1”
“Analog In 2”

155
156
158
159

158 [DC Brake Level]

Defines the DC brake current level injected into
the motor when “DC Brake” is selected as a stop
mode or when using the motor DC injection
brake feature through a digital input. This also
sets the braking current level when “Fast Stop” is
selected.
The DC braking voltage used in this function is
created by a PWM algorithm and may not
generate the smooth holding force needed for
some applications. Refer to the PowerFlex
Reference Manual.

Default:

Min/Max:

Units:

[Rated Amps]

0/[Rated Amps] x 1.5
(Equation yields approximate
maximum value.)
0.1 Amps

361

366

159 [DC Brake Time]

Sets the amount of time DC brake current is
“injected” into the motor. Not used for “Ramp to
Hold” which will apply DC braking continuously.
See page

143

.

Default:

Min/Max:
Units:

0.0 Secs

0.0/90.0 Secs
0.1 Secs

155

158

160 [Bus Reg Ki]

Sets the responsiveness of the bus regulator.

Default:

Min/Max:
Units:

450

0/5000
1

161
162

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 16

for symbol descriptions

Values

Rela

ted

FV

FV

ATTENTION: If a hazard of injury due to movement of equipment or
material exists, an auxiliary mechanical braking device must be used.

ATTENTION: This feature should not be used with synchronous or
permanent magnet motors. Motors can be demagnetized during
braking.