Appendix a - supplemental drive information, Communication configurations, Typical programmable controller configurations – Rockwell Automation 20B PowerFlex 700 AC Drives Vector Control (v4.001 and up) User Manual

Page 97: Appendix a, Supplemental drive information, Appendix

Advertising
background image

Rockwell Automation Publication 20B-UM002G-EN-P - July 2014

97

Appendix

A

Supplemental Drive Information

For product certifications and specifications, see PowerFlex 700 Adjustable
Frequency AC Drive Technical Data, publication

20B-TD001

.

Communication
Configurations

Typical Programmable Controller Configurations

Logic Command/Status Words

Table 13 - Logic Command Word

Topic

Page

Communication Configurations

97

IMPORTANT

If block transfers are programmed to continuously write information to the
drive, care must be taken to properly format the block transfer. If attribute 10 is
selected for the block transfer, values will be written only to RAM and will not
be saved by the drive. This is the preferred attribute for continuous transfers. If
attribute 9 is selected, each program scan will complete a write to the drives
non-volatile memory (EEprom). Since the EEprom has a fixed number of
allowed writes, continuous block transfers will quickly damage the EEprom. Do
Not assign attribute 9 to continuous block transfers. Refer to the individual
communications adapter User Manual for additional details.

Logic Bits

Command

Description

15

14

13

12

11

10

9 8 7 6 5 4 3 2 1 0

x Stop

(1)

0 = Not Stop
1 = Stop

x

Start

(1)(2)

0 = Not Start
1 = Start

x

Jog

0 = Not Jog
1 = Jog

x

Clear Faults

0 = Not Clear Faults
1 = Clear Faults

x

x

Direction

00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Hold Present Direction

x

Local Control

0 = No Local Control
1 = Local Control

Advertising