Precharge Board LED Indications

Precharge Board LED indicators are found on AC input drives, Frames 5…10.

HIM Indication

The LCD HIM also provides visual notification of a fault or alarm condition.

Manually Clearing Faults

Name

Color

State

Description

Power

Green

Steady

Indicates when precharge board power supply is operational

Alarm

Yellow

Flashing
[1]
[2]
[3]
[4]
[5]
[6]
[7]

Number in “[ ]” indicates flashes and associated alarm

(1)

:

Low line voltage (<90%).
Very low line voltage (<50%).
Low phase (one phase <80% of line voltage).
Frequency out of range or asymmetry (line sync failed).
Low DC bus voltage (triggers ride-through operation).
Input frequency momentarily out of range (40-65 Hz).
DC bus short circuit detection active.

(1) An alarm condition automatically resets when the condition no longer exists.

Fault

Red

Flashing
[2]
[4]

Number in “[ ]” indicates flashes and associated fault

(2)

:

DC bus short (Udc <2% after 20 ms).
Line sync failed or low line (Uac <50% Unom).

(2) A fault indicates a malfunction that must be corrected and can only be reset after cycling power.

Condition

Display

Drive is indicating a fault
The LCD HIM immediately reports the fault condition by displaying the
following.
“Faulted” appears in the status line
Fault number
Fault name
Time that has passed since fault occurred
Press the

key to regain HIM control.

Drive is indicating an alarm
The LCD HIM immediately reports the alarm condition by displaying the
following.
Alarm name (Type 2 alarms only)
Alarm bell graphic

Esc

F-> Faulted

Auto

0.0

Hz

Main Menu:

Diagnostics

Parameter

— Fault — F

5

OverVoltage
Time Since Fault

0000:23:52

F-> Power Loss

Auto

0.0

Hz

Main Menu:

Diagnostics

Parameter

Device Select

Step

1. Press the

key to acknowledge the fault. The fault information will be removed so that you can use the HIM.

2. Address the condition that caused the fault.

The cause must be corrected before the fault can be cleared.

3. After corrective action has been taken, clear the fault using one of these methods.

Press the

(Stop) key.

Cycle drive power.
Set parameter 240 [Fault Clear] to “1.”
“Clear Faults” on the HIM Diagnostic menu.

Esc