Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual

Page 100

Advertising
background image

100

Rockwell Automation Publication 1756-UM010B-EN-P - December 2011

100 Configuring the Configurable Flowmeter Module

5. Use ladder logic and a message instructions to send the new

configuration to your CFM module, see

page 89

.

O.Total[0].Overspeed

Decimal

BOOL

Enables the Overspeed alarm on output connected to

channel 0. When the Speed exceeds the Highest

Allowed Frequency value, this alarm is set.

0 = No Alarm

1 = Alarm Enabled

1

O.Total[0].Acceleration

Decimal

BOOL

Enables the Acceleration alarm on output connected

to channel 0. When the absolute acceleration

exceeds the Acceleration Alarm value, this alarm is

set.

0 = No Alarm

1 = Alarm Enabled

1

I.Status[0].FreqAverage

Float

REAL

Displays frequency averaged over the Meter samples

on channel 0

I.Status[0].Acceleration

Float

REAL

Displays acceleration on channel 0 as calculated by

using AccelCalculation samples

I.Ch0OverrangeAlarm

Decimal

BOOL

Displays whether overrange alarm was set on

channel 0

0 = alarm was not set

1 = alarm was set

I.Ch1AccelerationAlarm

Decimal

BOOL

Displays whether acceleration alarm was set on

channel 0

0 = alarm was not set

1 = alarm was set

I.Ch1OverspeedAlarm

Decimal

BOOL

Displays whether overspeed alarm was set on

channel 0

0 = alarm was not set

1 = alarm was set

Table 7 - Tag Changes Required for High Resolution Frequency Mode

Name

Style

Data type

Definition

Enter this

Value