84 Configuring the Configurable Flowmeter Module

Altering the Default

Configuration

If you want to alter or view the default configuration, click on Next. On the
next wizard screen, you can change the CFM module’s configuration as shown
below.

After you are finished with the screen above, you must access the module tags,
via the Tag Editor, to make additional configuration changes, see

page 85

.

If you want a Major Fault on the
Controller
to occur if there is connection
failure with the I/O module, click here

This Fault box is empty when you
are offline. If a fault occurs while
the module is online, the type of
fault will be displayed here

Inhibit the connection to the module here

Adjust the Requested Packet Interval here.

Click here to finish this portion of configuration
and move to the Tag Editor, see

page 85

.

IMPORTANT: Minimum RPI values:

 50 ms for one channel in totalizer mode
 100 ms for two channels in totalizer mode
 5 ms for one channel in high resolution

frequency mode

 10 ms for two channels in high resolution

frequency mode

 55 ms for one channel in each mode

IMPORTANT

Two additional wizard screens appear during initial module
configuration. The screens are used during online
application monitoring but are shown below to give you an
accurate description of the screens that appear during initial
configuration.