Alarms in high resolution frequency mode – Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual

Page 40

Advertising
background image

40

Rockwell Automation Publication 1756-UM010B-EN-P - December 2011

40 Configurable Flowmeter Module Features and Operational Modes

Highest Allowed Frequency

Use Highest Allowed Frequency to set the trigger point for
Frequency. In other words, set this value so that when the input reaches it, the
outputs are energized. This value is also used for
the Overspeed Alarm.

Acceleration Alarm Value

Use Acceleration Alarm to set the trigger point for Acceleration.
In other words, set this value so that when the input reaches it,
the outputs are energized. This value is also used for the
Acceleration Alarm.

Frequency Average

With Frequency Average, the CFM divides meter counts by a user-defined
sample interval (up to 2 seconds) to determine the Frequency Average.

Acceleration

Use Acceleration to determine an acceleration value over a user-defined
number of samples.

Alarms in High Resolution Frequency Mode

High Resolution Frequency mode offers the following alarms:

 Overrange Alarm
 Overspeed Alarm
 Acceleration Alarm

You must enable each alarm. When any of the alarms occur, it is latched and
remains on until the user resets the alarm.

Sample Configuration for High Resolution Frequency Mode

To see a sample configuration for a 1756-CFM module using high resolution
frequency mode, including the use of all the features mentioned in the
previous section, see

page 97

.