18 Configurable Flowmeter Operation in the ControlLogix System

1756-CFM modules follow these basic operational steps, as shown in

Figure 2

.

1. The Logix controller establishes a connection to the CFM module and

downloads configuration via ladder logic and message instructions.

2. Flowmeters transmit input signals to the CFM module.

3. The 1756-CFM module calculates volume from accumulated pulse

counts as engineering units.

4. Rather than being scanned by an owner-controller, the 1756-CFM

module periodically multicasts its status to the controller. (see

Requested

Packet Interval (RPI) on page 23

.) The 1756-CFM module also

multicasts its status to controllers connected by a listen-only connection
(

page 22

).

5. The Logix owner-controller processes the data it received from the

1756-CFM module and returns the appropriate data.

Figure 2 - 1756-CFM Basic Operational Steps

IMPORTANT

A 1756-CFM module’s communication, or multicasting,
behavior varies depending upon whether it operates in the
local chassis or in a remote chassis. The following sections
detail the differences in data transfers between these
set-ups.

42732

Input
device

1

2

4

5

3

1756-CFM

Logix controller