Module status information, Configurable flowmetering channels, Flowmeter inputs – Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual

Page 34: Gate inputs

Advertising
background image

34

Rockwell Automation Publication 1756-UM010B-EN-P - December 2011

34 Configurable Flowmeter Module Features and Operational Modes

Module Status Information

The ControlLogix CFM module has status indicators on the front of the
module that allow you to check the module health and operational status.

The following status can be checked with the LED indicators:

Input point status - display indicates a particular points status,

including specific indicators for the input F and Z points for each
channel

Output point status - display indicates the status of two output points

on the module

For an example of the status indicators, see

page 115

.

Configurable Flowmetering Channels

The CFM module offers two configurable Flowmetering channels. Each
channel uses two Flowmeter inputs (F0 & F1) and two corresponding gate
inputs (Z0 & Z1).

Flowmeter Inputs

Two Flowmeter inputs (F0 & F1) are available on your CFM module. The
inputs are capable of receiving the following input signals:

 +/- 30V peak from passive Magnetic Pickups
 5V DC logic (TTL compatible)
 12-24V DC powered preamp outputs

Gate Inputs

The CFM module offers two gate inputs (Z0 & Z1). You can wire the inputs
for single-ended or differential applications and can accept signals at 5V DC or
12-24V DC.

IMPORTANT

The Z0 and Z1 inputs can have different voltages
connected to them simultaneously.