Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual

Page 155

Advertising
background image

155

Rockwell Automation Publication 1756-UM010B-EN-P - December 2011

Configure Output Behavior with RSLogix 5000 Version 16 and Earlier 155

Specify the Configurable On/Off Behavior

1. In the previously existing program, select the Controller Tag folder and

view the Monitor Tags tab.

2. Expand the CFM_B_C tag until you reach the

CFM_B_C.OutputWindow data tags.

3. In the Value column of the CFM_B_C.OutputWindow data tags, enter

the desired the On and Off frequency limits.

See

Table 5 on page 58

for more information about determining your

On/Off frequency limits.

4. Edit existing tag references throughout the project so they link to the

appropriate, newly-added, user-defined tags.

For example, if the tag reference is Local:5:I.Status.FreqAverage, change
it to the corresponding user-defined tag, CFM_IN.Status.FreqAverage.

IMPORTANT

Test the configuration before implementing the changes
into your production process.