Installing the Configurable Flowmeter Module 71

Standard Prover/Detector Wiring Example

1. Detectors #1 and #2 must be wired in parallel.
2. Customer VCC may be used to power detectors. In this case, though,

the maximum current on the wiring arm must be less than 4A.

3. The wiring example above shows a 12-24V DC standard prover

connected to the module. If you use a 5V DC standard prover, make sure
the positive wire is connected to the 5V terminal (e.g. Z0 5V DC).

4. If separate power sources are used, do not exceed the specified

isolation voltage.