58 Configurable Flowmeter Module Features and Operational Modes

Configurable Output

Behaviors

Firmware revision 2.4 enables you to configure the 1756-CFM module outputs
to turn on or off at specified frequency counts.

Three types of behaviors, listed in the Frequency Values and Resulting
Behaviors table, can be configured with the use of firmware revision 2.4. Use
this table as a reference when determining on/off frequency values later in the
configuration procedure.

Table 5 - On/Off Frequency Behaviors

Frequency Value Behavior
FreqOn = 0.0

FreqOff = 0.0

Typical behavior when firmware revision 1.x is used. If the

C.OutputSetup[X].TriggerOn value is 1, a frequency count

corresponding to the TriggerOn frequency activates the

Ch[X]Overspeed Alarm, which latches and requires additional

programming to unlatch.

FreqOff greater

than FreqOn

The specified channel turns off when the frequency count is at or

above the specified FreqOff value. The specified channel turns on

when the frequency count is at or above the FreqOn value. For

example:

FreqOn greater

than FreqOff

The specified channel turns on when the frequency count is at or

above the specified FreqOn value. The specified channel turns off

when the frequency count is at or below the specified FreqOff value.

For example:

FreqOff = 60
FreqOn = 20

Time

20

60

= On

Fr

eq

ue

nc

y

FreqOn = 60
FreqOff = 20

= On

Time

60

20

Fr

eq

ue

ncy