116 Troubleshooting the Configurable Flowmeter Module

Table 10 - CFM Module Status Indicators

LED

indicators

This display Means

Take this action

OK

Steady green

light

The inputs are being

multicast and in normal

operating state.

None

OK

Flashing

green light

The module has passed

internal diagnostics but is

not actively controlled.

Configure the module.

OK

Flashing red

light

Previously established

communication has timed

out.

Check controller and

chassis communication

OK

Steady red

light

The module must be

replaced.

Replace the module.

Input

(F, Z)

Off

The input is turned off.

The input is not in use.

A wire is disconnected.

If you need to use the input,

check wiring connections

Input

(F, Z)

Steady

yellow

The input is in normal

operating state.

None

Output

(0, 1)

Off

The output is turned off.

The output is not in use.

If you need to use the

output, check wiring

connections and your

ladder logic application.

Output

(0, 1)

Steady

yellow

The output is in normal

operating state.

None