110

Rockwell Automation Publication 1756-UM010B-EN-P - December 2011

110 Configuring the Configurable Flowmeter Module

C.Operations[0].FilterResolution

Float

REAL

Sets resolution of the Speed calculation

based on the raw counts

0 = default of 0.00001

0.00001 = resolution of + 1 count of 100,000

raw counts.

0.166

C.Operations[0].SampleTime

Float

REAL

Sets time for a sample to be taken.

(2.0 second maximum sample time for high

resolution frequency mode and 5.0 seconds

for totalizer mode)

0.5

C.Operations[0].kFactStruct.kFactorForChan[0]

Float

REAL

K-factor 0 for Channel 0 when frequency is <

FreqAtKFactor[1]

600.0

C.Operations[0].kFactStruct.kFactorForChan[1]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor [1]

600.0

C.Operations[0].kFactStruct.kFactorForChan[2]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor [2]

550.0

C.Operations[0].kFactStruct.kFactorForChan[3]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor [3]

0.0

C.Operations[0].kFactStruct.kFactorForChan[4]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor [4]

0.0

C.Operations[0].kFactStruct.kFactorForChan[5]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor [5]

0.0

C.Operations[0].kFactStruct.kFactorForChan[6]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor [6]

0.0

C.Operations[0].kFactStruct.kFactorForChan[7]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor [7]

0.0

C.Operations[0].kFactStruct.kFactorForChan[8]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor [8]

0.0

C.Operations[0].kFactStruct.kFactorForChan[9]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor [9]

0.0

C.Operations[0].kFactStruct.kFactorForChan[10] Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor

[10]

0.0

C.Operations[0].kFactStruct.kFactorForChan[11] Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor

[11]

0.0

C.Operations[0].kFactStruct.kFactorForChan[12] Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor

[12]

0.0

C.Operations[0].kFactStruct.FreqAtKFactor[0]

Float

REAL

0.0

C.Operations[0].kFactStruct.FreqAtKFactor[1]

Float

REAL

Freq[1] for KFactor [1]

100.0

C.Operations[0].kFactStruct.FreqAtKFactor[2]

Float

REAL

Freq[2] for KFactor [2]

500.0

C.Operations[0].kFactStruct.FreqAtKFactor[3]

Float

REAL

Freq[3] for KFactor [3]

0.0

C.Operations[0].kFactStruct.FreqAtKFactor[4]

Float

REAL

Freq[4] for KFactor [4]

0.0

Table 9 - Tag Changes Required for Totalizer Mode Using Filler Function

Name

Style

Data type

Definition

Enter

this

Value

Advertising