Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual

Page 144

Advertising
background image

144

Rockwell Automation Publication 1756-UM010B-EN-P - December 2011

144 Frequency Accuracy

Use the following equation to calculate frequency accuracy in totalizer mode
for frequency period:

Speed

For speed, you must know the filter resolution. Use the following equation to
calculate frequency accuracy in totalizer mode for speed:

EXAMPLE

For example, in an application with the following
conditions:

 0.5s time period
 123Hz frequency
 25°C operating temperature

accuracy is determined with the following equation:

EXAMPLE

For example, in an application with the following
conditions:

 0.001 filter resolution
 25°C operating temperature

accuracy is determined with the following equation:

Accuracy =

(1) x (100)

(T

s

) x (F

in

)

Accuracy =

(1) x (100)

(0.5) x (123)

Accuracy = 1.626 + 0.005

+ 0.005%

Accuracy = +/- 1.631%

Value is added to
accuracy to account
for the crystal error

Accuracy = Resolution x 100

Accuracy = 0.1 + 0.005

Accuracy = (0.001 x 100) + 0.005

Accuracy = +/- 0.105%

Value is added to
accuracy to account
for the crystal error