Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual

Page 99

Advertising
background image

99

Rockwell Automation Publication 1756-UM010B-EN-P - December 2011

Configuring the Configurable Flowmeter Module 99

C.Operations[0].SampleTime

Float

REAL

Sets time for a sample to be taken.

(2.0 second maximum sample time for high resolution

frequency mode and 5.0 second maximum sample

time for totalizer mode)

0.033

C.Operations[0].HighestAllowedFreq

Float

REAL

User-defined value between MinDetectableFreq and

120,000

When the frequency reaches this level, it sets the

Overspeed alarm limit

3700

C.Operations[0].AccelAlarmValue

Float

REAL

Sets Acceleration alarm limit
-Maximum acceleration (cycles per second

2

)

<AccelAlarmValue< +Maximum acceleration (cycles
per second

2

)

100

C.OutputSetup[0].TriggerOn

Decimal

SINT

Sets when output 0 energizes

0 = No Action

1 = Frequency

2 = Acceleration

3 = Full Flow State (N/A in this mode)

4 = Trickle Flow State (N/A in this mode)

5 = Prover Run State (N/A in this mode)

6 = Prover Range State (N/A in this mode)

0

C.OutputSetup[0].TieToCounter

Ties a channel to output 0

0 = No connection

1 = Connect Channel0 to Output0

2 = Connect Channel1 to Ouput0

0

O.Total[0].CombinedCorrectionFactor

Float

REAL

0 = Default value of 1.0

Use this value to convert from Hz to RPMs. Results

are displayed in Frequency Average only

60

O.Total[0].Overrange

Decimal

BOOL

Enables the Overrange alarm on output connected to

channel 1. When the Frequency Average exceeds

100KHz, this alarm is set.

0 = No Alarm

1 = Alarm Enabled

0

Table 7 - Tag Changes Required for High Resolution Frequency Mode

Name

Style

Data type

Definition

Enter this

Value