Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual

Page 103

Advertising
background image

103

Rockwell Automation Publication 1756-UM010B-EN-P - December 2011

Configuring the Configurable Flowmeter Module 103

C.Operations[0].MeterFactor

Float

REAL

Calibration Adjust for metering reading

applied after K-factor correction. Typically,

this factor is between 0.8 and 1.2 but the

module restricts the value>0.

1.0

C.Operations[0].FilterResolution

Float

REAL

Sets resolution of the Speed calculation

based on the raw counts

0 = default of 0.00001

0.00001 = resolution of + 1 count of 100,000

raw counts.

0.166

C.Operations[0].SampleTime

Float

REAL

Sets time for a sample to be taken.

(2.0 second maximum sample time for high

resolution frequency mode and 5.0 seconds

for totalizer mode)

0.5

C.Operations[0].kFactStruct.kFactorForChan[0]

Float

REAL

K-factor 0 for Channel 0 when frequency is <

FreqAtKFactor[1]

600.0

C.Operations[0].kFactStruct.kFactorForChan[1]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor

[1]

600.0

C.Operations[0].kFactStruct.kFactorForChan[2]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor

[2]

550.0

C.Operations[0].kFactStruct.kFactorForChan[3]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor

[3]

0.0

C.Operations[0].kFactStruct.kFactorForChan[4]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor

[4]

0.0

C.Operations[0].kFactStruct.kFactorForChan[5]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor

[5]

0.0

C.Operations[0].kFactStruct.kFactorForChan[6]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor

[6]

0.0

C.Operations[0].kFactStruct.kFactorForChan[7]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor

[7]

0.0

C.Operations[0].kFactStruct.kFactorForChan[8]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor

[8]

0.0

C.Operations[0].kFactStruct.kFactorForChan[9]

Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor

[9]

0.0

C.Operations[0].kFactStruct.kFactorForChan[10] Float

REAL

This tag is an ordered pair with tag

C.Operations[0].kFactStruct.FreqAtKFactor

[10]

0.0

Table 8 - Tag Changes Required for Totalizer Mode Using Prover Function

Name

Style

Data type

Definition

Enter this

Value

Advertising