152 Configure Output Behavior with RSLogix 5000 Version 16 and Earlier

Configure a 1756-CFM Module for Use in an Existing Application

Complete this configuration process if you are using the 1756-CFM module
with an existing application.

Add the 1756-Generic Profile to the Program

1. In RSLogix 5000 software, open a project that contains programming

for an existing 1756-CFM module.

2. In the I/O configuration, delete the existing 1756-CFM module.

3. In the I/O configuration, add a new module.

Use the generic 1756 module profile listed in Other module types.

4. Name the new module according to your preference.

5. In the New Module dialog box, enter the Connection Parameters and

Comm Format exactly as displayed below.

6. Click OK.

The Module Properties dialog box displays.

7. Set the module RPI to 100.

8. Click OK.

The 1756-Generic module is now in the I/O configuration.

Enter the slot number
that matches the
location of the
1756-CFM module in
your ControlLogix
chassis.