Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual
Page 113

113
Rockwell Automation Publication 1756-UM010B-EN-P - December 2011
Configuring the Configurable Flowmeter Module 113
O.Total[0].Overflow
Decimal
BOOL
Enables the Overflow alarm on output
connected to channel 0. When the Total
Counts exceeds the Roll Over value, this
alarm is set.
0 = No Alarm
1 = Alarm Enabled
0
O.Total[0].Overspeed
Decimal
BOOL
Enables the Overspeed alarm on output
connected to channel 0. When the Speed
exceeds the Highest Allowed Frequency
value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
1
O.Total[0].Acceleration
Decimal
BOOL
Enables the Acceleration alarm on output
connected to channel 0. When the absolute
acceleration exceeds the Acceleration Alarm
value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
1
I.Status[0].FillState
Decimal
SINT
Displays current state of module for channel
0. The following states are possible:
0 = Filler not active
1 = Filler Enabled only, waiting for start
2 = Timed Trickle Flow complete, not filled
3 = Full Flow (Fill mode =1)
4 = Timed Trickle Flow (Fill mode =1)
5 = Full Flow (Fill mode =0)
6 = Fill Total Target Trickle Flow
(Fill mode = 0)
7 = Fill complete
Table 9 - Tag Changes Required for Totalizer Mode Using Filler Function
Name
Style
Data type
Definition
Enter
this
Value