Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual

Page 113

Advertising
background image

113

Rockwell Automation Publication 1756-UM010B-EN-P - December 2011

Configuring the Configurable Flowmeter Module 113

O.Total[0].Overflow

Decimal

BOOL

Enables the Overflow alarm on output

connected to channel 0. When the Total

Counts exceeds the Roll Over value, this

alarm is set.

0 = No Alarm

1 = Alarm Enabled

0

O.Total[0].Overspeed

Decimal

BOOL

Enables the Overspeed alarm on output

connected to channel 0. When the Speed

exceeds the Highest Allowed Frequency

value, this alarm is set.

0 = No Alarm

1 = Alarm Enabled

1

O.Total[0].Acceleration

Decimal

BOOL

Enables the Acceleration alarm on output

connected to channel 0. When the absolute

acceleration exceeds the Acceleration Alarm

value, this alarm is set.

0 = No Alarm

1 = Alarm Enabled

1

I.Status[0].FillState

Decimal

SINT

Displays current state of module for channel

0. The following states are possible:

0 = Filler not active

1 = Filler Enabled only, waiting for start

2 = Timed Trickle Flow complete, not filled

3 = Full Flow (Fill mode =1)

4 = Timed Trickle Flow (Fill mode =1)

5 = Full Flow (Fill mode =0)

6 = Fill Total Target Trickle Flow

(Fill mode = 0)

7 = Fill complete

Table 9 - Tag Changes Required for Totalizer Mode Using Filler Function

Name

Style

Data type

Definition

Enter

this

Value