Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual

Page 105

Advertising
background image

105

Rockwell Automation Publication 1756-UM010B-EN-P - December 2011

Configuring the Configurable Flowmeter Module 105

C.OutputSetup[0].TriggerOn

Decimal

SINT

Sets when output 0 energizes

0 = No Action

1 = Frequency

2 = Acceleration

3 = Full Flow State (N/A in this mode)

4 = Trickle Flow State (N/A in this mode)

5 = Prover Run State

6 = Prover Range State

0

C.OutputSetup[0].TieToCounter

Ties a channel to output 0

0 = No connection

1 = Connect Channel0 to Output0

2 = Connect Channel1 to Ouput0

0

C.Ch0ProverDirection

Decimal

BOOL

Defines the direction of a prover connected

to Channel 0.

0 = unidirectional prover

1 = bidirectional prover

0

C.Ch0LowFreqClear

Decimal

BOOL

Enables the minimum detectable frequency

level for Channel 0.

Set the bit to 1 to enable it

1

C.Operations[0].OperationalMode

Decimal

SINT

Sets the module’s operational mode.

0 = OFF

1 = Totalizer Mode

2 = Non-Resettable Totalizer Mode

3 = High Resolution Frequency Mode

2

O.OutputControl[0].0

Decimal

BOOL

Manually sets the operation of outputs

connected to channel 0.

0 = Module operation of outputs

1 = Override Output0 to 0

2 = Override Output0 to 1

0

O.Total[0].ProverEnable

Decimal

BOOL

Enables the prover operation on output

connected to channel 0. Once this bit is

enabled, the module waits for output Z

0

to

energize before beginning prover

operations.

0 = Prover operation is disabled

1 = Prover operation is enabled

0

O.Total[0].Overrange

Decimal

BOOL

Enables the Overrange alarm on output

connected to channel 0. When the

Frequency Period exceeds 100KHz, this

alarm is set.

0 = No Alarm

1 = Alarm Enabled

0

O.Total[0].Overflow

Decimal

BOOL

Enables the Overflow alarm on output

connected to channel 0. When the Total

Counts exceeds the Roll Over value, this

alarm is set.

0 = No Alarm

1 = Alarm Enabled

0

Table 8 - Tag Changes Required for Totalizer Mode Using Prover Function

Name

Style

Data type

Definition

Enter this

Value

Advertising