Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual
Page 107

107
Rockwell Automation Publication 1756-UM010B-EN-P - December 2011
Configuring the Configurable Flowmeter Module 107
5. Use ladder logic and a message instructions to send the new
configuration to your CFM module, see
.
I.Status[0].ProverTotal
Float
REAL
Corrected/compensated volume received on
Channel 0 during prover cycle.
Prover total resets when the ProverEnable
transitions from 0-1.
Prover total concurrently accumulates with
net volume, and must be saved if subtracted
from the NetVolume for single and multiple
prover verifications.
I.Ch0AccelerationAlarm
Decimal
BOOL
Displays whether acceleration alarm was
set on channel 0
0 = alarm was not set
1 = alarm was set
I.Ch0OverspeedAlarm
Decimal
BOOL
Displays whether overspeed alarm was set
on channel 0
0 = alarm was not set
1 = alarm was set
I.Ch0OverrangeAlarm
Decimal
BOOL
Displays whether overrange alarm was set
on channel 0
0 = alarm was not set
1 = alarm was set
I.Ch0OverflowAlarm
Decimal
BOOL
Displays whether overflow alarm was set on
channel 0
0 = alarm was not set
1 = alarm was set
Table 8 - Tag Changes Required for Totalizer Mode Using Prover Function
Name
Style
Data type
Definition
Enter this
Value