Schematics

What This Appendix

Contains

Use this appendix to understand the internal logic of the CFM module.

Follow the wiring practices described in your system-level installation manual
when wiring your I/O devices. This includes:

 routing conductors
 grounding practices
 use of shielded cables

Input Circuits

The CFM module input logic consists of:

 flowmeter input circuits
 gate input circuits

Flowmeter Inputs

The flowmeter input circuit combines operational amplifier principles with
solid state devices to provide constant logic pulses internal to the CFM
module. The circuit is designed to interface with both active or passive sensor
inputs by accepting any pulse output device (such as turbine flowmeter,
magnetic pickup or digital pickup).