Changing configuration during cfm module operation, Using ladder logic – Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual

Page 88

Advertising
background image

88

Rockwell Automation Publication 1756-UM010B-EN-P - December 2011

88 Configuring the Configurable Flowmeter Module

Changing Configuration

During CFM Module

Operation

After the CFM module has begun operation, you can only change
configuration by using ladder logic and message instructions.

Follow these steps to change CFM module configuration during operation:

1. Access the CFM data structures through the tag monitor to make

specific configuration changes, see

page 85

.

2. Use ladder logic and a configuration message instruction to send the

configuration changes to the CFM module, see below through

page 94

.

Using Ladder Logic

You must use ladder logic to perform the following operations on your CFM
module:

 change configuration
 perform run time services

Ladder logic uses message instructions to exchange data between the
controller and CFM module. You can access the ladder logic by
double-clicking on the Main Routine portion of the MainProgram.

Double-click here to
enter the Main Routine