122 Software Configuration Tags

C.Ch0PreTrigger

Decimal

BOOL

Enables the PreTrigger on Channel 0 for full flow.

Set the bit to 1 to enable it

C.Ch1PreTrigger

Decimal

BOOL

Enables the PreTrigger on Channel 1 for full flow.

Set the bit to 1 to enable it

C.Operations[0].OperationalMode

Decimal

SINT

Sets the module’s operational mode.

0 = OFF

1 = Totalizer Mode

2 = Non-Resettable Totalizer Mode

3 = High Resolution Frequency Mode

C.Operations[0].FilterControl

Decimal

SINT

The following values placed in

the appropriate word invoke the following filters.

0x01 = Hardware (sub 100Hz RC) filter for F0

0x02 = Hardware (sub 100Hz RC) filter for G0

0x03 = 2 Hardware filters (sub 100Hz RC) for F0 and G0

0x04 = Firmware filter, 1 second debounce filter used for

prover applications for G0 (ignore/disable the gate for 1

second after an initial pulse)

0x06 = both the Hardware and Firmware filters for G0

0x07 = all filters above: Hardware (sub 100Hz RC) for F0

and G0 and the Firmware, 1 second debounce on prover for

G0

C.Operations[0].MeterSamples

Decimal

SINT

C.Operations[0].ThresholdControl

Decimal

SINT

Sets module threshold control

0 = 50mV threshold

1 = 1.3V (TTL) threshold

2 = 4.0V threshold

C.Operations[0].CalculationType

Decimal

SINT

Sets calculation type

0 = Counts/K-factor x MeterFactor correction x CCF

1 = Counts/K-factor x MeterFactor correction x AGA 7

compensation of CCF if CCF is not equal to 0.0

C.Operations[0].AccelCalculation

Decimal

SINT

Number of past samples to use to calculate an

acceleration value.

Sample range is 0 to 255.

C.Operations[0].FillMode

Decimal

SINT

Sets the Trickle mode for engineering units or time.

0 = Engineering units

1 = Time

C.Operations[0].MinDetectableFreq

Float

REAL

User-defined value from 0 - 100,000.

Sets FreqAverage, FreqPeriod, Speed, GrossRate, and

NetRate reading to 0 when calculated value is less than

value entered. GrossVolume, and NetVolume do not

increment below this value even though TotalCounts

increments over time.

C.Operations[0].HighestAllowedFreq

Float

REAL

User-defined value between MinDetectableFreq and

120,000

When the frequency reaches this level, it sets the

Overflow alarm limit

Table 13 - Configurable Flowmeter Module Configuration Tags