112 Configuring the Configurable Flowmeter Module

C.Ch0LowFreqClear

Decimal

BOOL

Enables the minimum detectable frequency

level for Channel 0.

Set the bit to 1 to enable it

1

C.Ch0PreTrigger

Decimal

BOOL

Enables the PreTrigger on Channel 0 for full

flow.

Set the bit to 1 to enable it

1

C.Operations[0].FillMode

Decimal

SINT

Sets the Trickle mode to complete on fill total

target or time.

0 = Fill total target (Engineering units)

1 = Time (seconds)

0

O.OutputControl[0].0

Decimal

BOOL

Manually sets the operation of outputs

connected to channel 0.

0 = Module operation of outputs

1 = Override Output0 to 0

2 = Override Output0 to 1

0

O.Total[0].FillEnable

Decimal

BOOL

Enables the filling operation on output

connected to channel 0.

0 = Fill operation is disabled

1 = Fill operation is enabled.

0

O.Total[0].FillStart

Decimal

BOOL

Begins filling operation when Fill Enable is

enabled on output connected to channel 0.

0 = Do not begin filling

1 = Begin filling

0

O.Total[0].FillHold

Decimal

BOOL

Holds/pauses filling operation on output

connected to channel 0

0 = Continue filling operation

1 = Hold/pause filling operation

0

O.Total[0].FillTotalTarget

Float

REAL

Target for Fill Complete, except when Fill

Transition is greater than this value.

100

O.Total[0].FillTransition

Float

REAL

When fill cycle is started, trickle flow is

initiated when the Fill Total is equal to or

greater than this value. Full flow is initiated

when the Fill Total is less than this value.

75

O.Total[0].FillTransitionTimer

Float

REAL

When timed trickle flow is selected, the

status remains ON for this time during this

state.

The value must be changed prior to entering

the trickle flow state.

1.0

O.Total[0].Overrange

Decimal

BOOL

Enables the Overrange alarm on output

connected to channel 0. When the Frequency

Period exceeds 100KHz, this alarm is set.

0 = No Alarm

1 = Alarm Enabled

0

Table 9 - Tag Changes Required for Totalizer Mode Using Filler Function

Name

Style

Data type

Definition

Enter

this

Value