Operating in high resolution frequency mode – Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual

Page 36

Advertising
background image

36

Rockwell Automation Publication 1756-UM010B-EN-P - December 2011

36 Configurable Flowmeter Module Features and Operational Modes

Operating in

High Resolution

Frequency Mode

In High Resolution Frequency mode, the CFM module calculates frequency
over a user-defined time period up to 2 seconds. Frequency sampling begins
on the leading edge of the first pulse and ends on the next pulse to occur after
the sampling period expires.

This figure shows a CFM module in a turbine shaft speed monitoring
application in high resolution frequency mode.

You must calculate a resolution for this mode. Use the following equation to
calculate resolution.

This table lists sample F

in

and T

sample

values and the corresponding resolution.

The values listed in

Table 4

are listed for example purposes. Specific values will

change according to your application.

42731

CV

Pulse output

Fuel

Monitors fuel flow
and total gallons

Generator

Electricity

Shaft
encoder

Turbine

Shaft speed

1756-CFM

Logix controller:

 monitors shaft speed
 performs PID calculations
 adjusts valve by a 1756-OF6VI

analog output module.

1756-OF6VI

Table 4 - Sample Resolutions

F

in

T

sample

Resolution

60Hz

0.033 seconds

0.00045Hz

5000Hz

0.020 seconds

0.0625Hz

50,000Hz

0.050 seconds

0.25Hz

F

in

(250 x 10

-9

)

T

sample

Resolution =

Where:

 F

in

is the input frequency

 T

sample

is the sample time period