56

Rockwell Automation Publication 1756-UM010B-EN-P - December 2011

56 Configurable Flowmeter Module Features and Operational Modes

 If the input frequency is greater than 100Hz-200Hz, the K-factor is

interpolated as follows:

 If the input frequency is greater than 200Hz-300Hz, the K-factor is

interpolated as follows:

 If the input frequency is greater than 300Hz, the K-factor used

is always 100.0. There is no K-factor calculation over 100Hz.

To use Gross Rate, you must set the K-factor values in Module Tags, as shown
below.

K-factor = (f

in

- 100.0) x

(71.0 - 25.0)

(200.0 - 100.0)

x 25.0

K-factor = (f

in

- 200.0) x

(111.0 - 71.0)

(300.0 - 200.0)

x 71.0

Name

Style

Data type

Value

Change during

operation

C.Operations[0].kFactStruct.kFactorForChan[0]

Float

REAL

25.0

1

Yes

C.Operations[0].kFactStruct.kFactorForChan[1]

Float

REAL

25.0

1

Yes

C.Operations[0].kFactStruct.kFactorForChan[2]

Float

REAL

71.0

Yes

C.Operations[0].kFactStruct.kFactorForChan[3]

Float

REAL

111.0

Yes

C.Operations[0].kFactStruct.kFactorForChan[4]-

C.Operations[0].kFactStruct.kFactorForChan[12]

Float

REAL

0

Yes

C.Operations[0].kFactStruct.FreqAtKFactor[0]

Float

REAL

0.0

Yes

C.Operations[0].kFactStruct.FreqAtKFactor[1]

Float

REAL

100.0

Yes

C.Operations[0].kFactStruct.FreqAtKFactor[2]

Float

REAL

200.0

Yes

C.Operations[0].kFactStruct.FreqAtKFactor[3]

Float

REAL

300.0

Yes

C.Operations[0].kFactStruct.FreqAtKFactor[4]-

C.Operations[0].kFactStruct.FreqAtKFactor[12]

Float

REAL

0

Yes

1

To avoid discontinuity when interpolating Gross Rate, make sure the values in C.Operations[0].kFactStruct.kFactorForChan[0] and C.Operations[0].kFactStruct.kFactorForChan[1] match.

IMPORTANT

For more information on setting values in the Module
Tags, see

Configuring the Configurable Flowmeter Module

5 on page 77

.