63

Rockwell Automation Publication 1756-UM010B-EN-P - December 2011

Installing the Configurable Flowmeter Module 63

Power Requirements

This module receives power from the 1756 chassis power supply and requires
2 sources of power from the backplane:

 300mA at 5.1V DC
 16mA at 24V DC

Add this current/power value (1.7W) to the requirements of all other modules
in the chassis to prevent overloading the power supply.

ATTENTION

!

The ControlLogix system has been agency certified using
only the ControlLogix RTBs (catalog numbers
1756-TBNH and 1756-TBSH). Any application that
requires agency certification of the ControlLogix system
using other wiring termination methods may require
application specific approval by the certifying agency.