Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual

Page 98

Advertising
background image

98

Rockwell Automation Publication 1756-UM010B-EN-P - December 2011

98 Configuring the Configurable Flowmeter Module

Follow the steps below to configure your CFM module for high resolution
frequency mode.

1. Create a new module, see

page 80

.

2. Set all communications options, including:

 name
 communication format
 slot number
 minor revision
 electronic keying
 RPI - For this application, the minimum RPI = 5 ms

See pages

81

to

84

.

3. Access the module tags via the Tag Editor, see

page 85

.

4. Change only the tags listed in

Table 7

. You can ignore all other tags;

they do not affect high resolution frequency mode

Table 7 - Tag Changes Required for High Resolution Frequency Mode

Name

Style

Data type

Definition

Enter this

Value

C.Ch0LowFreqClear

Decimal

BOOL

Enables the minimum detectable frequency level for

Channel 0.

Set the bit to 1 to enable it

1

C.Operations[0].OperationalMode

Decimal

SINT

Sets the module’s operational mode.

0 = OFF

1 = Totalizer Mode

2 = Non-Resettable Totalizer Mode

3 = High Resolution Frequency Mode

3

C.Operations[1].OperationalMode

Decimal

SINT

Sets the module’s operational mode.

0 = OFF

1 = Totalizer Mode

2 = Non-Resettable Totalizer Mode

3 = High Resolution Frequency Mode

0

C.Operations[0].AccelCalculation

Decimal

SINT

Number of past samples to use to calculate an

acceleration value.

Sample range is 0 to 255.

50

C.Operations[0].MeterFactor

Float

REAL

Calibration Adjust for metering reading applied after

K-factor correction. Typically, this factor is between

0.8 and 1.2 but the module restricts the value>0.

0

C.Operations[0].FilterResolution

Float

REAL

Sets resolution of the Speed calculation based on the

raw counts

0 = default of 0.00001

0.00001 = resolution of + 1 count of 100,000 raw

counts.

0.00001