Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual

Page 97

Advertising
background image

97

Rockwell Automation Publication 1756-UM010B-EN-P - December 2011

Configuring the Configurable Flowmeter Module 97

Sample Configuration for

High Resolution

Frequency Mode

High resolution frequency mode provides speed control of machinery such as
turbines where shutdown on acceleration or speed is required independent of
the owner-controller. Speed is calculated without the K-factor but includes the
meter factor and CCF for special calculations.

When using this mode, you may calculate resolution by using the following
equation to calculate resolution.

The values listed in

Table 6

are listed for example purposes. Specific values will

change according to your application.

This section offers a sample configuration to configure your CFM module for
high resolution frequency mode. In this configuration, channel 0 is configured
and channel 1 is left unused.For a detailed explanation of the features available
in this mode, see

page 36

.

Table 6 - Sample Resolutions

F

in

T

sample

Resolution

60Hz

0.033 seconds

0.00045Hz

5000Hz

0.020 seconds

0.0625Hz

50,000Hz

0.050 seconds

0.25Hz

F

in

(250 x 10

-9

)

T

sample

Resolution =

Where:

 F

in

is the input frequency

 T

sample

is the sample time period