148 Configure Output Behavior with RSLogix 5000 Version 16 and Earlier

Configure the 1756-CFM for Use in a New Application

Complete this procedure if you are using the 1756-CFM module and the
configurable on/off feature in a new application.

Add the 1756-Generic Profile to the Program

1. In RSLogix 5000 software, create a new project named CFM_DEMO.

2. Specify the controller type, revision number, chassis type, and slot

number according to your ControlLogix controller chassis.

3. In the I/O Configuration folder, add a new module.

4. Use the Generic 1756 Module profile listed in Other module types.

5. In the New Module dialog box, enter the Connection Parameter

information exactly as displayed below.

6. Click OK.

The Module Properties dialog box opens.

7. Set the module RPI to 100.

8. Click OK.

The 1756-Generic module is now in the I/O configuration.

Enter the slot number
that matches the
location of the
1756-CFM module in
your ControlLogix
chassis.