114 Configuring the Configurable Flowmeter Module

5. Use ladder logic and a message instructions to send the new

configuration to your CFM module, see

page 89

.

I.Status[0].TotalCounts

Decimal

DINT

Displays actual pulses counted by the counter

connected to the channel 0

I.Status[0].FillTotal

Float

REAL

Same calculation as Net Volume

during fill cycle.

I.Status[0].GrossVolume

Float

REAL

Total Counts during each

Sample/K-factor x Meter Factor as occurs on

channel 0

I.Status[0].NetVolume

Float

REAL

Total Counts during each

Sample/K-factor x MeterFactor x CCF) as

occurs on channel 0

I.Status[0].GrossRate

Float

REAL

Total Counts in Meter Sample/ (K-factor x

Sample Interval) x Meter Factor as occurs on

channel 0

I.Status[0].NetRate

Float

REAL

Total Counts in Meter Sample/ (K-factor x

Sample Interval) x Meter Factor x CCF as

occurs on channel 0

I.Ch0AccelerationAlarm

Decimal

BOOL

Displays whether acceleration alarm was set

on channel 0

0 = alarm was not set

1 = alarm was set

I.Ch0OverspeedAlarm

Decimal

BOOL

Displays whether overspeed alarm was set on

channel 0

0 = alarm was not set

1 = alarm was set

I.Ch0OverrangeAlarm

Decimal

BOOL

Displays whether overrange alarm was set on

channel 0

0 = alarm was not set

1 = alarm was set

I.Ch0OverflowAlarm

Decimal

BOOL

Displays whether overflow alarm was set on

channel 0

0 = alarm was not set

1 = alarm was set

Table 9 - Tag Changes Required for Totalizer Mode Using Filler Function

Name

Style

Data type

Definition

Enter

this

Value