Trickle Function for Totalizer Mode

The trickle function is used with the filler function to improve volume
repeatability in a filling application. The trickle function requires two filling
lines and an optional discrete module to activate the trickle valve. Activation of
the valve should be sized for worst case volume at least 100 ms based on
typical program scan = 5 ms and an output module RPI = 25 ms.

For most of the filling process, the full flow state is assigned to one of the
module’s outputs. For more repeatable fills or to prevent overfills, the
pretrigger feature helps make sure that the full flow valve turns off before it
reaches the

Fill Transition

or

Fill Total Target

volume.

When the filling application reaches the user-defined

Fill Transition

point, the

trickle totalizer mode changes the application from the full flow line to the
trickle flow line. This slower line allows the application to finish the filling
process without any waste.

For more information on the

Fill Transition

feature, see

page 57

.

The filler function can be used in any of the following conditions:

 Starting with the trickle flow
 Filling with the full flow only
 Restarting the timed trickle flow
 Starting the trickle flow prior to the fill transition
 Restarting full flow while in trickle flow

Using the Trickle feature in previously mentioned conditions requires specific
configuration changes.