Using a Prover

A prover is used for the calibration of liquid meters in custody transfer
applications. This calibration is done by comparing a metered throughput to a
known volume in the prover. When enabled, the prover total updates while the
spheroid moves between two detectors and is then compared to the
predetermined volume of the prover section to ascertain the meter factor.

If you are using the Totalizer or Nonresettable Totalizer mode for capturing
meter counts during a prover calibration, you have the option of selecting
either of these types of provers:

 Unidirectional - With a unidirectional prover, the CFM module:

begins updating Prover Total when the spheroid passes the first

detector

stops updating Prover Total when the spheroid passes the second

detector

 Bidirectional - With a bidirectional prover, the CFM module:

begins updating Prover Total when the spheroid passes the first

detector

stops counting when the spheroid passes the second detector (Prover

Total is updated at this time - intermediate value returned)

continues updating when the spheroid returns past the second

detector

stops updating when the spheroid returns past the first detector

(Prover Total Count Value is updated at this time)

This figure shows an example of a spheroid and detectors.

19884

detectors

spheroid