132 Software Configuration Tags

Output Tags

You must use the Output tags to change CFM module configuration during
operation.

Table 15

lists and defines CFM Output tags:

Table 15 - Configurable Flowmeter Module Output Tags

Name

Style

Data type

Definition

O.Total[0].AlarmEnables

Binary

SINT

O.Total[0].Overrange

Decimal

BOOL

Enables the Overrange alarm on output connected to

channel 0. When the Frequency Period exceeds 100KHz,

this alarm is set.

0 = No Alarm

1 = Alarm Enabled

O.Total[0].Overflow

Decimal

BOOL

Enables the Overflow alarm on output connected to

channel 0. When the Total Counts exceeds the Roll Over

value, this alarm is set.

0 = No Alarm

1 = Alarm Enabled

O.Total[0].Overspeed

Decimal

BOOL

Enables the Overspeed alarm on output connected to

channel 0. When the Speed exceeds the Highest

Allowed Frequency value, this alarm is set.

0 = No Alarm

1 = Alarm Enabled

O.Total[0].Acceleration

Decimal

BOOL

Enables the Acceleration alarm on output connected to

channel 0. When the absolute acceleration exceeds the

Acceleration Alarm value, this alarm is set.

0 = No Alarm

1 = Alarm Enabled

O.Total[0].Control

Binary

SINT

O.Total[0].Reset

Decimal

BOOL

Rising edge resets the count

O.Total[0].Load

Decimal

BOOL

Reserved

O.Total[0].ProverEnable

Decimal

BOOL

Enables the prover operation on output connected to

channel 0. Once this bit is enabled, the module waits

for output Z

0

to energize before beginning prover

operations.

0 = Prover operation is disabled

1 = Prover operation is enabled

O.Total[0].FillEnable

Decimal

BOOL

Enables the filling operation on output connected to

channel 0.

0 = Fill operation is disabled

1 = Fill operation is enabled.

O.Total[0].FillStart

Decimal

BOOL

Begins filling operation when Fill Enable is enabled on

output connected to channel 0.

0 = Do not begin filling

1 = Begin filling

O.Total[0].FillHold

Decimal

BOOL

Holds/pauses filling operation on output connected to

channel 0

0 = Continue filling operation

1 = Hold/pause filling operation