Rockwell Automation 9303 DRIVE TOOLS 32 VER 2.50 GETTING STARTED User Manual

Page 49

Advertising
background image

Setting Up DH+ Direct Communications

5-9

Setting Up Communications in a DriveTools32 Application

Before a DriveTools32 application can communicate with a drive, you need to
configure the application.

1.

Start the DriveTools32 application.

2.

In the Options menu, select Communication Setup. The Communication
Setup
dialog box appears.

3.

Click the DH+ tab.

4.

Under Connect Type, select DF1 (KF2) To Data Highway Plus (DH+).

5.

In the Enter INTERCHANGE Port Mapping # field, type the number of
the KT:0 port used by the DF1 driver in the RSLinx Configure Client
Applications
dialog box.

Important: To view the KT Port number used by DF1 communications, select
Configure Client Applications in the RSLinx Communications menu.

6.

In the Enter Serial Communication Port field, type the number of the
computer communications port that is being used.

7.

In the Enter The Port Baud Rate field, type the baud rate that your
communications module and port are using.