Setting Up ControlNet Direct Communications

Using a 1203-CN1
Module to Connect
to a ControlNet
Network

A 1203-CN1 module lets you connect to a ControlNet network via its serial port.

Figure 7.2
Connecting to a ControlNet Network via a 1203-CN1 Module

Before using this type of connection, you must do the following:

Note the station number of the module on the ControlNet network. It is
displayed on the front of the module as a decimal value. You must convert
this value from the displayed decimal value to an octal value.
You can
use the Windows Calculator program set in scientific mode to do the
calculation.

Note the serial baud rate of the module. View Serial Port Rate (Parameter
21) to find the baud rate. Refer to the ControlNet Communications Module
User Manual
for information on viewing and editing module parameters.

Remember that you can access 99 stations on the ControlNet network.

In RSLinx, you need to configure RS-232 point-to-point or multi-drop serial
communications (Refer to Chapter 3). As you configure RSLinx, you need to:

Enter the correct station number as an octal value in the Configure Allen-
Bradley DF1 Communications Device
dialog box.

Select the correct baud rate in the Configure Allen-Bradley DF1
Communications Device
dialog box.

In a DriveTools32 application, you must set up RS-232 point-to-point
communications (Refer to Chapter 3). As you configure the DriveTools32
application, you must:

Enter the correct baud rate in the Communication Setup dialog box.

Enter the station number to which you intend to connect as an octal value in
the SCANport Network Connect to Drive dialog box.

Note that you cannot use the WHO button if you are using a point-to-point
connection.

Important: Verify that you have connected to the correct product before you
use the DriveTools32 application to edit parameters or control the product.

1203-SFC
cable

1203-CN1

1203-CN1

ControlNet Channel B

ControlNet Channel A

Decimal: Node 8

Octal: Node 10

Decimal: Node 52

Octal: Node 64