Rockwell Automation 9303 DRIVE TOOLS 32 VER 2.50 GETTING STARTED User Manual
Page 90

9-6
Setting Up DeviceNet Direct Communications
Setting Up Communications in a DriveTools32 Application
Before a DriveTools32 application can communicate with a drive, you must
configure the application. To do so, you need to:
1.
Start the DriveTools32 application.
2.
In the Options menu, select Communication Setup. The Communication
Setup dialog box appears.
3.
Click the DeviceNet tab.
4.
Under Connect Type, select DeviceNet using Allen-Bradley 1784-PCD
(PCIDS) CARD.
5.
In the Enter INTERCHANGE Port Mapping # field, type the number of
the KT:0 port used by the DeviceNet driver in the RSLinx Configure Client
Applications dialog box.
Important: To view the KT Port number used by the DeviceNet driver, select
Configure Client Applications in the RSLinx Communications menu.
6.
If you are using a 1336 FORCE and its drive firmware version is 0.10,
select 1336T Two Word Header (used ONLY for 1336T version 0.10).
7.
Click OK.