4-68

LiquiFlo 1.5 AC Drive, Software Reference Version 1.2

Selects the type of input signal being used for analog input 1 and 2.

Enables/disables the square root function for each analog input.

This function should be enabled if the input signal varies with the square of the
quantity (i.e., drive speed) being monitored. The square root function is scaled such
that the input range is the same as the output range. For example, if the input is set up
as a unipolar voltage input, then the input and output ranges of the square root
function will be 0 to 10 volts.

320

Anlg In Config

Range:

See figure 4.29

Default:

See figure 4.29

Access:

0

Path: Inputs & Outputs>Analog Inputs

See also:

322, 323, 325, 326

Figure 4.29 – Anlg In Config (320)

0

x

x

1

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Current
0 =Voltage
x =Reserved

Bit #

Factory Default Bit Values

Analog In 1

Analog In 2

Nibble 1

Nibble 2

Nibble 3

Nibble 4

321

Anlg In Sqr Root

Range:

See figure 4.30

Default:

See figure 4.30

Access:

1

Path: Inputs & Outputs>Analog Inputs

See also:

Figure 4.30 – Anlg in Sqr Root (321)

0

x

x

0

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Enable
0 =Disable
x =Reserved

Bit #

Factory Default Bit Values

Analog In 1

Analog In 2

Nibble 1

Nibble 2

Nibble 3

Nibble 4

Advertising