4-74

LiquiFlo 1.5 AC Drive, Software Reference Version 1.2

361
362
363
364
365
366

Digital In1 Sel
Digital In2 Sel
Digital In3 Sel
Digital In4 Sel
Digital In5 Sel
Digital In6 Sel

Range:

0 = Not Used
1 = Enable
2 = Clear Faults

1

3 =Aux Fault4 = Stop - CF

2

5 = Start
6 = Fwd/Reverse

2

7 = Run

3

8 = Run Forward

3

9 = Run Reverse

3

10 = Jog
11 = Jog Forward
12 = Jog Reverse
13 = Stop Mode B
14 = Bus Reg Md B
15 = Speed Sel 1

4

16 = Speed Sel 2

4

17 = Speed Sel 3

4

18 = Auto/Manual
19 =Local
20 = Acc2 & Dec2
21 = Accel 2
22 = Decel 2
23 = MOP Inc
24 = MOP Dec
25 = Exc Link
26 = PI Enable
27 = PI Hold
28 = PI Reset
29 = Pwr Loss Lvl
30 = Precharge En

Default:

See table 4.4

Access:

361-366 = 0

Path: Inputs & Outputs>Digital Inputs

See also:

96, 100, 124, 140, 156, 162, 194, 380

1

When Digital In”x” Sel is set to option 2 (Clear Faults), the stop key cannot be used to clear a fault condition.

2

Typical 3-Wire Inputs. These require that only 3-wire functions are chosen. Including 2-wire selections will cause a type 2 alarm.

3

Typical 2-Wire Inputs. These require that only 2-wire functions are chosen. Including 3-wire selections will cause a type 2 alarm.

4

To access Preset Speed 1, set Speed Ref A Sel to Preset Speed 1. See table 4.3