94 speed ref b hi, 95 speed ref b lo, 96 tb man ref sel – Rockwell Automation Liqui-Flo 1.5 General Purpose and Vector Duty User Manual

Page 53

Advertising
background image

Parameter Descriptions

4-21

Scales the upper value of the Speed Ref B Sel (93) selection when the source is an
analog input.

Scales the lower value of the Speed Ref B Sel (93) selection when the source is an
analog input.

Specifies the manual speed reference source when a digital input is configured for
auto/manual and manual reference mode is active.

!

ATTENTION: Removing and replacing the LCD OIM while the drive is
running may cause an abrupt speed change if the LCD OIM is the
selected reference source, but is not the selected control source. The
drive will ramp to the reference level provided by the OIM at the rate
specified in Accel Time 1 (140), Accel Time 2 (141), Decel Time 1 (142)
and Decel Time 2 (143). Be aware that an abrupt speed change may
occur depending upon the new reference level and the rate specified in
these parameters. Failure to observe this precaution could result in bodily
injury.

94

Speed Ref B Hi

Range:

-/+Maximum Speed [0.1 Hz]

Default:

Maximum Speed

Access:

0

Path: Speed Command>Speed References

See also:

82

95

Speed Ref B Lo

Range:

-/+Maximum Speed [0.1 Hz]

Default:

0.0 Hz

Access:

0

Path: Speed Command>Speed References

See also: 81

96

TB Man Ref Sel

Range:

1 = Analog In 1
2 = Analog In 2
3-8 = Reserved
9 = MOP Level

Default:

2 = Analog In 1

Access:

0

Path: Speed Command>Speed References

See also:

97, 98

Advertising